Water hardness and tap water in Karlum
Kreis Nordfriesland, Schleswig-Holstein · Postcode 25926
This page is a translation of the German version; the German page is authoritative. German version · Report a translation error
- Limits of the Drinking Water OrdinancemetAll tested parameters (15), at the waterworks
- Water hardness10.8 °dH, mediumNo legal limit, only a range
- Data coverageCore parameters: 5 of 7Score based on complete data
Verified drinking-water values
| Parameter | Value | Limit (TrinkwV) | Sampling date | Source | Status |
|---|---|---|---|---|---|
| Nitrate | < 0.5 mg/L | 50 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Nitrite | < 0.005 mg/L | 0.5 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Lead | < 0.001 mg/L | 0.01 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Uranium | < 0.00001 mg/L | 0.01 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Mercury | < 0.0001 mg/L | 0.001 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Copper | < 0.003 mg/L | 2 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Chromium | < 0.0005 mg/L | 0.025 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Chloride | 34 mg/L | 250 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Sulphate | 48 mg/L | 250 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Sodium | 17.5 mg/L | 200 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Calcium | 71.1 mg/L | – | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Magnesium | 3.88 mg/L | – | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| pH | 7.48 | 6.5–9.5 | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Total hardness | 10.8 °dH (medium) | no legal limit | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Electrical conductivity | 479 µS/cm | – | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Fluoride | 0.08 mg/L | 1.5 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Iron | < 0.01 mg/L | 0.2 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Manganese | < 0.005 mg/L | 0.05 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
| Ammonium | < 0.02 mg/L | 0.5 mg/L | 5 August 2026 | Wasserversorgung Drei Harden | verified |
Note from the test report (in the German original): Wasserversorgung Drei Harden · Prüfbericht der AGROLAB Umwelt GmbH, Probe vom 05.08.2026 am Werkausgang des Wasserwerks Karlum in Niebüll. Der Verband veröffentlicht diese eine Analyse; sein Brunnenfeld liegt laut Wasserschutzgebietsverordnung von 2013 in der Gemarkung Karlum. Laut BDEW-Wasserportal liegen der Gemeindemittelpunkt von Karlum und vier Prüfpunkte rund 1,5 km darum im Gebiet des Verbands. Ob die ganze Gemeinde dieses Wasser bekommt, sagt verbindlich der Versorger. Die Werte gelten ab Wasserwerk.
Background on household plumbing, not a measurement: in Karlum, 74 % of buildings with living space were built before 1970, and a further 5 % between 1970 and 1979 (Zensus 2022, Statistisches Bundesamt, dl-de/by-2-0). (Zensus 2022) According to the German Environment Agency (Umweltbundesamt), lead pipes exist at most in houses built before 1973 – and by no means in all of them. Whether there are any in your house is known to the owner or a plumber. (UBA)
What the values mean for Karlum
- Lead – not detectable at the waterworks. Lead gets into the water almost only through old lead pipes in household plumbing, not via the supplier.
- Uranium – not detectable at the waterworks (limit 10 µg/L).
- pH 7.48 – within the range of the Drinking Water Ordinance (6.5 to 9.5). The pH determines how corrosive the water is in household plumbing.
Water hardness in Karlum in everyday life
At 10.8 °dH, Karlum is in the hardness range “medium” (soft: below 8.4 °dH, medium: 8.4–14 °dH, hard: above 14 °dH).
- Dose detergent for the hardness range “medium”.
- As a rule of thumb, descale the kettle about every four to six weeks and the coffee machine as the manufacturer recommends.
- A limescale protection device is not a must at medium hardness; regular descaling is often enough.
Baby food and low sodium: tap water in Karlum next to the bottled-water thresholds
Bottled water may only be labelled “suitable for preparing infant food” („geeignet für die Zubereitung von Säuglingsnahrung“) if it keeps to the maximum levels of the German Mineral and Table Water Ordinance (Mineral- und Tafelwasser-Verordnung, Annex 6). Here the published values for Karlum are shown next to them, each substance on its own. This is a comparison with labelling thresholds for bottled water, not a statement on whether your tap water is suitable for baby food. (Min/TafelWV, Anlage 6)
For context: the German Environment Agency (Umweltbundesamt) considers preparing baby food with bottled water carrying this label necessary only in rare cases, for example when tap water is temporarily allowed to contain more than 50 mg/l nitrate. (UBA 2016, p. 59) Water from lead pipes in the house is always unsuitable for infants. (UBA 2020, p. 16) The values apply at the waterworks.
| Substance | Maximum level | Value in Karlum |
|---|---|---|
| Sodium | 20 mg/l | 17.5 mg/l – not above |
| Nitrate | 10 mg/l | below the detection limit (0.5 mg/l) – not above |
| Nitrite | 0.02 mg/l | below the detection limit (0.005 mg/l) – not above |
| Sulphate | 240 mg/l | 48 mg/l – not above |
| Fluoride | 0.7 mg/l | 0.08 mg/l – not above |
| Manganese | 0.05 mg/l | below the detection limit (0.005 mg/l) – not above |
| Arsenic | 0.005 mg/l | not in the report |
| Uranium | 0.002 mg/l | below the detection limit (0.00001 mg/l) – not above |
Against the other thresholds of Annex 6, the water would qualify as: low in sodium (“suitable for a low-sodium diet”) (Sodium 17.5 mg/l, threshold below 20 mg/l).
Questions about baby food are answered by your midwife, your paediatrician and the health office (Gesundheitsamt).
Frequently asked questions about tap water in Karlum
Can you drink the tap water in Karlum?
According to the verified values, yes: All tested parameters with a legal limit (15) meet the limits set by the German Drinking Water Ordinance (TrinkwV). WaterScore: 100 out of 100 (data coverage: 5 of 7 core parameters). This applies to the water from the waterworks – restrictions can only arise from old household plumbing.
How hard is the water in Karlum?
The total hardness is 10.8 °dH – hardness range “medium”. Dose detergent for the hardness range “medium”.
Is there PFAS in the tap water in Karlum?
The published analysis by Wasserversorgung Drei Harden that we evaluated gives no PFAS value. This does not mean there is no PFAS in the water; there is simply no figure for it. Since 12 January 2026, a limit of 0.1 µg/l has applied to the sum of PFAS-20. The supplier can tell you whether PFAS was measured and with what result.
Do I need to filter my tap water in Karlum?
Based on the verified supplier values, a filter is not necessary. It can make sense if you do not like the taste. If you suspect lead pipes in an old building, a filter does not help; a laboratory analysis at the tap does – that is a question of the household plumbing, not of the water leaving the works.
WaterScore
- Total100 / 100
- Chemical safety100 / 100
- Heavy metals100 / 100
- Nutrients100 / 100
- General parameters100 / 100
- Data timeliness100 / 100
- Data quality100 / 100
Data coverage: 5 of 7 core parameters. Not in the test report: Arsenic and PFAS (sum). Missing parameters are neither estimated nor counted as harmless: the score is based only on the values available. It is not a health assessment and says nothing about the water beyond the service connection. Methodology v4: how we calculate the WaterScore.
Evidence: cite and check
- Trinkwasseranalyse Wasserwerk Karlum, Werkausgang, Probe vom 05.08.2026 (AGROLAB, Auftrag 2529311) (Wasserversorgung Drei Harden) · SHA-256 of the evaluated file: 6f40f3e8e5b6a144…, checked on 2 November 2026
Suggested citation: Trinkwassermonitor (2026): Tap water in Karlum. Values according to the water supplier’s test report, sampling date 5 August 2026; at the waterworks, not household plumbing. https://trinkwassermonitor.ink/en/tap-water/karlum/
JSON: /api/v1/evidence?city=karlum
Data as of: 5 August 2026 · verified: 19 of 19 evaluated parameters.
This page shows only verified test data with sources, or states explicitly where data is missing (no estimated values). Cite as: “Trinkwassermonitor (2026). Tap water in Karlum. Retrieved from https://trinkwassermonitor.ink/en/tap-water/karlum/.”