TrinkwassermonitorTap water in Germany

Water hardness and tap water in Tettenweis

Landkreis Passau, Bayern · Postcode 94167

This page is a translation of the German version; the German page is authoritative. German version · Report a translation error

Short answer: The tap water in Tettenweis has a total hardness of 17.5 °dH, hardness range “hard” (as of 26 May 2026). All tested parameters with a legal limit (10) meet the limits set by the German Drinking Water Ordinance (TrinkwV). Source: test report by Ruhstorfer Gruppe. WaterScore (provisional): 100 out of 100 – the test report contains only 2 of 7 core parameters.

Verified drinking-water values

ParameterValueLimit (TrinkwV)Sampling dateSourceStatus
Nitrate25 mg/L
50 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Nitrite< 0.02 mg/L0.5 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Chloride53.7 mg/L
250 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Sulphate20 mg/L250 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Sodium88.6 mg/L
200 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Calcium90.5 mg/L–26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Magnesium21.2 mg/L–26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
pH7.376.5–9.526 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Total hardness17.5 °dH (hard)no legal limit26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Electrical conductivity820 µS/cm–26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Fluoride0.37 mg/L
1.5 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Iron0.013 mg/L0.2 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Manganese< 0.005 mg/L0.05 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified
Ammonium0.01 mg/L0.5 mg/L26 May 2026Zweckverband Wasserversorgung Ruhstorfer Gruppeverified

Note from the test report (in the German original): Ruhstorfer Gruppe · Analyse vom 26.05.2026 am Hochbehälter Ruhstorf, auf der Website des Zweckverbands veröffentlicht; ein Labor nennt die Seite nicht. Laut Zweckverband gelten diese Werte für alle Mitgliedsgemeinden außer Bad Griesbach i. Rottal. Die Leitfähigkeit ist im Labor bei 20 °C gemessen. Schwermetalle, PFAS und Bakterien enthält die Veröffentlichung nicht.

Is a value wrong or out of date? Report an error – we check every report against the original source.

Water at your own tap: The values describe the water the supplier delivers – not automatically the water at your tap. The water supplier is responsible up to the service connection (Hausanschluss); the building owner is responsible for the pipes beyond it. Lead can dissolve from lead pipes, leaded solder joints or old brass fittings, especially when water has stood in the pipes for a long time (stagnant water); this mainly affects buildings constructed before about 1973. If water has stood in the pipes for several hours, let it run until it comes out cool. If you suspect lead pipes, a lead analysis of the stagnant water by an accredited laboratory will help.

Background on household plumbing, not a measurement: in Tettenweis, 38 % of buildings with living space were built before 1970, and a further 13 % between 1970 and 1979 (Zensus 2022, Statistisches Bundesamt, dl-de/by-2-0). (Zensus 2022) According to the German Environment Agency (Umweltbundesamt), lead pipes exist at most in houses built before 1973 – and by no means in all of them. Whether there are any in your house is known to the owner or a plumber. (UBA)

What the values mean for Tettenweis

Water hardness in Tettenweis in everyday life

At 17.5 °dH, Tettenweis is in the hardness range “hard” (soft: below 8.4 °dH, medium: 8.4–14 °dH, hard: above 14 °dH).

Baby food and low sodium: tap water in Tettenweis next to the bottled-water thresholds

Bottled water may only be labelled “suitable for preparing infant food” („geeignet für die Zubereitung von Säuglingsnahrung“) if it keeps to the maximum levels of the German Mineral and Table Water Ordinance (Mineral- und Tafelwasser-Verordnung, Annex 6). Here the published values for Tettenweis are shown next to them, each substance on its own. This is a comparison with labelling thresholds for bottled water, not a statement on whether your tap water is suitable for baby food. (Min/TafelWV, Anlage 6)

Values at the waterworks next to the maximum levels for bottled water “suitable for infant food”
SubstanceMaximum levelValue in Tettenweis
Sodium20 mg/l88.6 mg/l – above
Nitrate10 mg/l25 mg/l – above
Nitrite0.02 mg/lbelow the detection limit (0.02 mg/l) – not above
Sulphate240 mg/l20 mg/l – not above
Fluoride0.7 mg/l0.37 mg/l – not above
Manganese0.05 mg/lbelow the detection limit (0.005 mg/l) – not above
Arsenic0.005 mg/lnot in the report
Uranium0.002 mg/lnot in the report

For context: the German Environment Agency (Umweltbundesamt) considers preparing baby food with bottled water carrying this label necessary only in rare cases, for example when tap water is temporarily allowed to contain more than 50 mg/l nitrate. (UBA 2016, p. 59) Water from lead pipes in the house is always unsuitable for infants. (UBA 2020, p. 16) The values apply at the waterworks. Questions about baby food are answered by your midwife, your paediatrician and the health office (Gesundheitsamt).

Frequently asked questions about tap water in Tettenweis

Can you drink the tap water in Tettenweis?

According to the verified values, yes: All tested parameters with a legal limit (10) meet the limits set by the German Drinking Water Ordinance (TrinkwV). WaterScore (provisional): 100 out of 100 – the test report contains only 2 of 7 core parameters. This applies to the water from the waterworks – restrictions can only arise from old household plumbing.

How hard is the water in Tettenweis?

The total hardness is 17.5 °dH – hardness range “hard”. Dose detergent for the hardness range “hard” – a larger amount is needed; a water softener for the washing machine can save detergent.

Is there PFAS in the tap water in Tettenweis?

The published analysis by Ruhstorfer Gruppe that we evaluated gives no PFAS value. This does not mean there is no PFAS in the water; there is simply no figure for it. Since 12 January 2026, a limit of 0.1 µg/l has applied to the sum of PFAS-20. The supplier can tell you whether PFAS was measured and with what result.

Do I need to filter my tap water in Tettenweis?

Based on the verified supplier values, a filter is not necessary. It can make sense if you do not like the taste. If you suspect lead pipes in an old building, a filter does not help; a laboratory analysis at the tap does – that is a question of the household plumbing, not of the water leaving the works.

Is the nitrate level in Tettenweis a concern?

The value of 25 mg/L is below the limit of 50 mg/L, but higher than in many other evaluated cities. The limit of the Drinking Water Ordinance also applies to preparing baby food; mineral water labelled “suitable for preparing infant food” („geeignet für die Zubereitung von Säuglingsnahrung“) may contain at most 10 mg/L nitrate. Boiling does not help against nitrate.

WaterScore

Data coverage: 2 of 7 core parameters. Not in the test report: Lead, Copper, Arsenic, Uranium and PFAS (sum). Missing parameters are neither estimated nor counted as harmless: the score is based only on the values available and is therefore provisional. It is not a health assessment and says nothing about the water beyond the service connection. Methodology v3: how we calculate the WaterScore.

Evidence: cite and check

Suggested citation: Trinkwassermonitor (2026): Tap water in Tettenweis. Values according to the water supplier’s test report, sampling date 26 May 2026; at the waterworks, not household plumbing. https://trinkwassermonitor.ink/en/tap-water/tettenweis/

JSON: /api/v1/evidence?city=tettenweis

Data as of: 26 May 2026 · verified: 14 of 14 evaluated parameters.

This page shows only verified test data with sources, or states explicitly where data is missing (no estimated values). Cite as: “Trinkwassermonitor (2026). Tap water in Tettenweis. Retrieved from https://trinkwassermonitor.ink/en/tap-water/tettenweis/.”